Guidelines for installation
Set up the boxes so that the heat exchanger remains accessible for an annual cleaning service.
The outputs indicated are based on a free air flow of 75% of the depth. If the free opening is smaller, a correction factor must be applied to calculate the heat output.
% Free air flow | Correction factor |
75 | 1.00 |
60 | 0.96 |
50 | 0.92 |
40 | 0.84 |
30 | 0.66 |